| Model |
AGS 10 |
AGS 20 |
AGS 30 |
AGS 40 |
AGS 60 |
AGS 80 |
AGS 100 |
AGS 120 |
| Capacity |
10kVA 9kW |
20kVA 18kW |
30kVA 27kW |
40kVA 36kW |
60kVA 54kW |
80kVA 72kW |
100kVA 90kW |
120kVA 108kW |
| Input |
| Rated voltage |
380/400/415V AC |
| Voltage range |
204- 242V AC (load ≤ 50%) 242-305V AC (load ≤ 70%) 305-520V AC (load ≤ 100%) |
| Rated frequency |
50/60Hz (auto-sense) |
| Frequency range |
40-70Hz |
| Power factor |
≥ 0.99 |
| Total harmonic distortion (THDI) |
≤ 3% |
| Bypass voltage range |
rated output voltage -40% - + 20% (settable via LCD) |
| Output |
| Voltage |
380/400/415V AC |
| Voltage regulation |
± 1% |
| Frequency |
battery mode: 50/60Hz mains mode: synchronized with utility frequency conversion mode: 50Hz input and 60Hz output or 60Hz input and 50Hz output |
| Waveform |
sinusoidal |
| Crest factor |
3:1 |
| Total harmonic distortion (THDV) |
≤ 1% (linear load) ≤ 5% (non-linear load) |
| Transfer time |
0 ms |
| Inverter overload capability |
102% - 127%: transfer to bypass in 10 minutes 127% - 150%: transfer to bypass in 1 minute > 150%: transfer to bypass in 0.5 seconds |
| Bypass overload capability |
≤ 150%: long time running > 150%: shut down in 10 seconds |
| Batteries |
| DC voltage |
± 192V (options: ± 204 ± 216/± 228/ ± 240 V) |
| Inbuilt battery of standard model |
12V/9Ah x 32 |
12V/9Ah x 64 |
extensible model only |
| Charging current |
1-12 A (settable via LCD) |
1-24 A (settable via LCD) |
1- 24 A (settable via LCD) 1- 48 A (optional) |
| System |
| Efficiency |
≥ 93% 98.5% in eco-friendly mode |
| Display panel |
5.7 inches LCD touchscreen |
| Alarm |
battery mode, low battery, fans fault |
| Max parallel numbers |
6 |
| EMI |
EN62040-2 |
| EMS |
IEC61000-4-2 (ESD) IEC61000-4-3 (RS) IEC61000-4-4 (EFT)IEC61000-4-5 (surge) |
| Communications |
| RS232/RS48/USB/dry contacts (standard) |
supports Windows 98/2000/2003/XP/Vista /2008/7/ 8/10 |
| SNMP (optional) |
power management from SNMP manager and web browser |
| Others |
| Protections |
overload, surge, short circuit, battery low voltage, battery overcharge, over-temperature |
| Humidity |
0 to 95% RH at 0- 40℃ (non-condensing) |
| Noise level |
≤ 60 dB |
| Dimensions |
(W) 600 x (D) 800 x (H) 1360mm |
(W) 600 x (D) 800 x (H) 1680mm |
| Packing dimensions |
(W) 720x (D) 920x (H) 1500mm |
(W) 720x (D) 920x (H) 1820mm |
Net/gross weight Without inbuilt battery |
Net weight: 180kg Gross weight: 200kg |
Net weight: 186 kg Gross weight: 205kg |
Net weight: 188kg Gross weight: 210kg |
Net weight: 227 kg Gross weight: 245kg |
Net weight: 231 kg Gross weight: 250kg |
Net weight: 316 kg Gross weight: 376kg |
Net weight: 354 kg Gross weight: 414kg |